Electrical Test Meters
A meter is how you prove a circuit is dead before you touch it. The wrong meter, damaged leads, or a meter set to the wrong function can cause shocks, arc flashes, and false “dead” readings.
- Electrical
- Maintenance
Choose the right meter
- Category (CAT) rating: match the meter to where you’re working. CAT III covers building distribution (panels, feeders); CAT IV covers the service entrance and utility connection. Use a meter rated at least for the highest category and voltage you’ll measure.
- Look for a listing mark from a nationally recognized testing lab.
- Use leads with finger guards and shrouded tips, rated the same as the meter.
Measurement categories
The CAT rating tells you how well a meter can survive a voltage spike (transient) without exploding in your hand. Spikes are bigger closer to the utility service.
| Category | Where it applies | Examples |
|---|---|---|
| CAT II | Plug-in loads and receptacle circuits | Appliances, portable tools, wall outlets |
| CAT III | Building distribution | Panelboards, feeders, bus duct, motors, hard-wired equipment, lighting circuits |
| CAT IV | Origin of the installation | Service entrance, utility meter, overhead or underground service drop |
A CAT IV 600 V meter is generally safer than a CAT III 1000 V meter at the service entrance. Look at both the category and the voltage.
Types of testers
- Digital multimeter (DMM): measures voltage, resistance, continuity and sometimes current. The most common meter.
- Two-pole voltage tester (solenoid or “wiggy” style): rugged, simple voltage checks; some load the circuit to avoid false “ghost” voltage readings.
- Clamp meter: measures current by clamping around one conductor, without breaking the circuit.
- Non-contact voltage tester (“tick tracer”): beeps near energized conductors. Useful for a quick check, but it can miss shielded cables, DC, and some faults.
- Insulation resistance tester (megohmmeter): applies high voltage to test insulation. Only trained workers should use it, on de-energized and isolated equipment.
- Permanently mounted absence-of-voltage testers: built into some panels so you can verify zero energy before opening the door.
Live-dead-live
- Test the meter on a known live source.
- Test the circuit you’re working on, phase to phase and phase to ground.
- Test the meter on the known live source again to prove it still works.
Safe use
- Inspect the meter and leads for cracks and exposed metal before each use.
- Select the correct function and range before connecting. Measuring voltage with the leads in the current (amps) jacks can cause an arc flash.
- Wear the PPE required for the voltage and arc flash hazard. See Arc Flash.
- Treat non-contact voltage testers as a quick check only, never as proof a circuit is dead.
- Keep your fingers behind the finger guards on the probes, and hook one lead on first when you can, so you only hold one probe.
- Don’t use a meter with a cracked case, a loose battery door or a blown fuse.
- Don’t use cheap, unrated leads or replace the meter’s fuses with ordinary fuses. Use the exact high-energy fuses the maker specifies.
- Don’t measure resistance or continuity on a circuit that could be live.
- Don’t rely on a meter with a low battery. It can read zero on a live circuit.
Meter and lead check
- Case not cracked, display readable, battery good
- CAT and voltage rating right for the job
- Leads rated the same as the meter, with no cuts, exposed metal or loose tips
- Leads in the correct jacks for the measurement
- Function and range set before connecting
- Live-dead-live test done
Testing for absence of voltage is energized work. Until you prove the circuit is dead, treat it as live, and wear the shock and arc flash PPE the task requires. Only qualified workers should do it. See Qualified vs. Unqualified Workers and Lockout/Tagout.
Standards & references
- NFPA 70E: Test instruments and equipment
- 29 CFR 1910.334(c): Test instruments and equipment
Last updated: