Variable Frequency Drives

A variable frequency drive (VFD) controls the speed of an electric motor by changing the frequency and voltage it supplies. VFDs run pumps, fans, conveyors and HVAC systems. Inside is high voltage, and some of it stays after the power is shut off.

Hazards

Safe work steps

  1. Read the drive's manual and the warning labels; note the wait time required after shutoff, often 5 to 15 minutes or more.
  2. Stop the drive and the motor. Open and lock out the upstream disconnect and any other power sources, including control power and bypass. See Lockout/Tagout.
  3. Wait the full time listed.
  4. Test for absence of voltage with a rated meter on line terminals, load terminals and the DC bus. Confirm the meter works before and after. See Absence of Voltage Testing.
  5. Discharge or verify low DC bus voltage as the maker instructs, only if you are qualified.
  6. Prevent the motor from being turned by the load (such as a windmilling fan), since it can generate voltage back into the drive.

Installation and commissioning

Warning: A drive's display going dark does not mean it is safe. Always test the terminals.