Fire Alarm & Sprinkler Impairments
Renovation, tie-ins and repairs often require shutting down sprinklers or fire alarms. That’s exactly when a fire is most likely, from hot work, temporary power and construction debris. An impairment plan keeps the building protected while the system is down.
- Sprinkler fitters
- Electricians
- Facility managers
- General contractors
Photo: red impairment tag hung on a sprinkler control valve during renovation work
Before shutting a system down
- Get approval from the building owner or facility manager
- Notify the fire department, the alarm monitoring company and the insurance carrier, as required
- Tag the valve or panel to show it’s out of service
- Limit the shutdown to the smallest area and shortest time possible
- Have parts, tools and people ready so work goes quickly
- Set up a fire watch for the impaired area
- Stop or tightly control hot work and other fire risks in the area
Fire watch during the impairment
- Trained people patrol the impaired areas, with extinguishers and a way to call the fire department.
- Many fire codes require a fire watch whenever sprinklers or alarms are out for a set number of hours.
- Keep a log of patrols.
Restoring the system
- Reopen valves fully and secure them.
- Test the system as required (like a main drain test or alarm test).
- Remove tags and notify everyone who was told about the shutdown.
Closed valves cause disasters. Some of the worst building fires happened because a sprinkler valve was left closed after work. Double-check that every valve is open and supervised before leaving.
Day-to-day protection
- Cover sprinkler heads during painting or dusty work only with approved covers, and remove them at the end of the shift.
- Keep storage at least 18 inches below sprinkler deflectors.
- Don’t hang anything from sprinkler pipes or heads.
- Keep smoke detector covers on only during dusty work, and coordinate with the alarm contractor.
- On buildings under construction, keep standpipes and fire department access working as the building rises. See NFPA 241.
Standards & references
- 29 CFR 1910.159: Automatic sprinkler systems
- NFPA 25: Inspection, testing and maintenance of water-based fire protection systems (impairment procedures)
- See also: Hot Work Permits · Fire Prevention