NFPA 10: Portable Fire Extinguishers

NFPA 10 is the standard fire codes use for portable fire extinguishers: which kind to buy, how many, where to hang them and how to keep them working. OSHA has its own extinguisher rules, and fire inspectors usually look to NFPA 10 for the details. This page is a plain-language overview, not a replacement for the standard.

Where NFPA 10 fits

See Fire Extinguishers at Work.

Choosing the right type

NFPA 10 matches extinguishers to the class of fire and the hazard level of the area:

Areas are rated light, ordinary or extra hazard, which affects the minimum size (rating) of the extinguisher and how far you may be from one. A bigger rating number means more fire-fighting capacity. See Flammable Liquids.

Placement

Inspection and maintenance

How oftenWhat happens
MonthlyA quick visual inspection: in its place, not blocked, gauge in the operating range, seal and pin in place, no damage. Record it (often on a tag).
AnnuallyA thorough check by a trained, qualified person, with a new tag showing the date
Every 6 years (stored-pressure dry chemical)Empty and internal maintenance
Every 5 or 12 years, depending on typeHydrostatic pressure test of the cylinder
After any useRecharge or replace

Extinguishers that are damaged, corroded or fail inspection must be taken out of service and replaced. Never use a loaner or hang one that has been discharged. See Extinguisher Inspections.

Training

People expected to use extinguishers should be trained. OSHA requires training when employees are expected to fight fires (and an annual review for those employees). Remember: fight only small fires, with the alarm sounded and a clear exit behind you. See Emergency Action Plans.

Checklist for a site

Note: Standards are updated every few years, and details differ by edition and local adoption. Check the edition your jurisdiction uses.

Standards & references

Last updated: