Cranes & Power Lines: Preventing Contact

Power line contact is one of the leading causes of crane deaths. The people most often killed aren’t the operators but the riggers and laborers touching the load or the crane. Electricity can also arc across the air without the boom ever touching the line. OSHA’s crane rule (29 CFR 1926.1407 to 1926.1411) sets out exactly how to plan for it.

Step 1: Check the 20-foot zone

Before assembly or operation, mark out the work zone and decide whether any part of the crane, load line or load could get closer than 20 feet to a power line (for lines up to 350 kV) if it moved to its maximum working radius. Over 350 kV, the distance is 50 feet. If the answer is no, you can work normally. If yes, pick one of the options below.

Treat every line as energized until the utility confirms it’s de-energized and visibly grounded at the site.

Step 2: Choose an option

  1. De-energize and ground the line through the utility or owner. This is the safest choice.
  2. Stay 20 feet away (50 feet for over 350 kV), using the protections below.
  3. Use the Table A distance, after getting the line voltage from the utility.
Line voltage (Table A)Minimum clearance
Up to 50 kV10 feet
Over 50 to 200 kV15 feet
Over 200 to 350 kV20 feet
Over 350 to 500 kV25 feet
Over 500 to 750 kV35 feet
Over 750 to 1,000 kV45 feet

Required protections when working near lines

If you aren’t de-energizing, the employer must:

Working closer than the Table A distance is only allowed in rare cases, with the utility’s involvement and many more precautions.

Traveling under lines

Lower the boom, use a dedicated spotter when you’ll pass close to lines, and remember that rough ground makes the boom bounce. OSHA has separate minimum clearances for cranes in transit with no load. See Overhead Power Lines.

If the crane contacts a line

See Equipment Contact with Power Lines.

Pre-lift power line checklist

Standards & references